  • 周世宁,陈维田,Burnett J.,邓柏澧.空调室内环境的气传微生物[J].环境科学学报,1997,17(4):498-501

  • 空调室内环境的气传微生物
  • A STUDY OF MICROORGANISMS IN AIR CONDITIONED INDOOR ENVIRONMENT
  • 基金项目:香港理工大学科学研究基金
  • 作者
  • 单位
  • 周世宁
  • 中山大学生命科学学院,广州 510275
  • 陈维田
  • 香港理工大学
  • Burnett J.
  • 香港理工大学
  • 邓柏澧
  • 香港理工大学
  • 摘要:对于当代许多人来说,一生中的绝大部分时间在室内度过,因此室内环境是最值得注重的.近年来生物污染问题已成了室内环境研究的新课题.
  • Abstract:The forced air flow sampling method was used to investigate microorganisms in the air conditioned indoor environments. In the investigated 50 samples, the concentration of microorganisms was in the range of 28-333 CFU/m 3. The bacteria were found more than the fungi. G positive bacteria were the dominant. The coagulase positive Staphylococcus had a detection positive rate of 78% in the samples. The dominant fungi species were Penicillium, Cladosporium, Aspergillus and yeast. The dominant bacteria were Staphylococcus, Micrococcus and Bacillus. The CFU, especially fungi CFU, in the indoor spaces was less than the outdoor air. The respirable and non respirable viable particles in the indoor air were collected and counted respectively. It was found that respirable viable particles had a higher percentage in indoor air than outdoor air. High concentration of microorganisms was found in fibrous insulation material and condensed water in the air duct. Gnegative bacteria, which can survive for a long period, was the dominating type in the condensate samples.